1.Name&Functions of parts on Front Panel:
Name |
Function |
Measured value (PV) display |
(1) Measured value display LED (red) · Displays current PV value on basic screen (screen 0-0). · Displays type of parameter on each respective parameter display screen. |
Target set value (SV) display |
(2) Target value display LED (green) · Displays current SV value on basic screen (screen 0-0). · Displays setting values on each respective parameter setting screen. |
Action display |
Displays status of controller. · RUN: Action display LED (green) Off: Standby or reset On: Running by fixed value control Flashing: Running by program · AT : Auto tuning LED (green) Off: Auto tuning not executed On: Auto tuning standby Flashing: Auto tuning being executed · MAN: Manual control LED (green) Off: Output by automatic control. Flashing: Output by manual control. · OUT1: Control output 1 (green) · OUT2: Control output 2 (green) For output by contact or SSR drive voltage: Off: Output is OFF. On: Output is ON. For voltage/current output: Brightness changes according to the output ratio. (Light brightly if output is 100% and dimly if output is 0%.) · EV1: Event output 1 (orange) · EV2: Event output 2 (orange) · EV3: Event output 3 (orange) Off: Event output is OFF. On: Event output is ON. Note: Always off if event output is not selected as an optional item. · COM: Communications mode (green) Off: Communications local mode On: Communications COM mode |
Operating keys |
· : Parameter key Displays the next screen in various screen groups Pressing and holding for at least 3 seconds on 0-0 screen displays 4-0 initial settings screen group. · : Down key Decrements setting values. · : Up key Increments setting values. · ENT : Enter key Enters setting values. Displays various screen groups if no SV values are being modified on the basic screen. RUN · RST : RUN/RST key Pressing and holding for at least 2 seconds in STBY (RST) status switches to EXE (RUN). Pressing and holding for at least 2 seconds during EXE (RUN) switches to STBY (RST). status. Fixed value control (FIX mode) STBY: Standby status EXE: Control execution status Program control (PROG mode) RST: Reset status RUN: Program execution status |
2.Instruction:
2-1Preliminary check
The controller has undergone sufficient quality control inspections, but you should check the specification code/appearance and
make sure you have all the accessories to make sure nothing is missing or damaged.
Compare the specification code on the case with the following to make sure it is the product you ordered.
The SRS10A Series offers a selection of two codes: SRS11A and SRS12A/13A/14A;
(1) Mode Code Check
(2).
Accessories check
Instruction manual 1 copy
Communication interface instruction manual (if communication optional item added) 1 copy
Programming function instruction manual (if programming function optional item added) 1 copy
Unit seals 1 sheet
Note: Receiving impedance for current input (250Ω, 0.1%), current detector for heater break alarm (CT) and terminal cover
are sold separately as optional items and are not included with the controller.
Note: In the event you want to inquire about a product defect, missing accessory or other matter, please contact our salesman directly by email.
2-2.: Notes before use
Do not press front panel keys with a hard or pointed object. Press lightly with your fingertips. To clean, wipe lightly with a dry cloth. Do not use solvents such as thinner.
3.Installation&Wiring:
3-1.Installation site( environmental conditions)
Environmental conditions for operations
The controller is designed to be used under the following conditions. Observe the following environmental conditions when using:a)Must be used in doors;b)Max. elevation: 2000m;c)Ambient temperature: -10 to 50°C;d)Ambient humidity: Max. 90%RH, no condensation;e)Transient over voltage category: II; f)Pollution class: 2 (IEC 60664);
#Caution:
Do not use the controller in the following locations.Doing so could lead to equipment failure, damage or fire.
· Places exposed to flammable or corrosive gases, oil mist, or excessive dust that could cause insulation to deteriorate.
· Places subject to vibration or impact
· Places near strong electric circuit or places subject to inductive interference
· Places exposed to water dripping or direct sunlight
· Places where the controller is struck directly by air from heater or air conditioner
3-2.Mounting:
Cut a hole for mounting the controller in the panel.The panel thickness should be 1.0 - 3.5 mm.
The controller is provided with tabs for mounting. Insert as is from the front surface of the panel.Controllers of the SRS10A Series are designed for mounting on the panel. Be sure to mount on the panel.
If mounted in series, provide ventilation so ambient temperature does not exceed 50°C due to temparature rise caused by heat generation.
#Caution:
In order to maintain safety and function, do not remove the case from the controller.
If the case of the controller has to be removed for replacement/repair, Pls contact our salesman directly by email;
3-3. External Dimensions &Panel Cutout:
3-4. Wiring
Take the following precautions when wiring:
(1)Wire in accordance with the terminal layout of section 3-5 and the terminal arrangement table of section 3-6. After wiring,
check and make sure the wiring is correct.
(2)Crimp-type terminals fit M3 screws. Use crimp-type terminals that are no wider than 6 mm.
(3)For thermocouple input, use a compensating conductor that matches the type of thermocouple.
(4)For R.T.D. input, resistance for lead wires should be a maximum of 5Ω per wire. All 3 wires should have the same resistance.
(5)Input signal wires must not be accommodated with a strong electric circuit in the same conduit or duct.
(6)Using shielded wiring (single point grounding) is effective for static induction noise.
(7)Making input wiring short and twisting at regular intervals is effective for electromagnetic induction noise.
(8)For power supply, use wiring or cable with sectional area of at least 1 mm² that offers the same performance as 600V vinyl
insulated wiring.
(9)Securely fasten the terminal element screw. Fastening torque: 0.5 N·m (5kgf·cm)
(10)If the instrument appears to be easily affected by power supply noise, use a noise filter to prevent malfunctioning.
Mount the noise filter on the grounded panel and make the wire connection between the noise filter output and power line
terminals of the controller as short as possible.
(11)Current transformer (CT) connection method (CT input optional)
#Caution:
Be sure to turn off power before wiring. Failure to do so could result in electric shock.
After wiring, do not touch terminal elements or other charged parts while conducting electricity. Failure to do.so could result in electric shock.
3-5. Terminal Layout
Wire in accordance with the following terminal layout and terminal arrangement table.
3-6. Terminal Arrangement Table:
3-7.Operation Preparations:
Before operating the controller, you should first check the wiring and carry out the following by screen group setting method.
There is however no need to change the settings that have been set at the factory or already been made by the manufacturer.
1. Wiring check
Make sure the wiring to the connection terminals is correct. Incorrect wiring could result in burnout.
2. Power ON
Turn on the operating power. The displays, etc., light when power is supplied to the controller.
3. Measuring range setting
Select code from Measuring Range Codes of "4-58 Measuring range codes setting screen" of 4 screen group and enter.
Select temperature unit of "4-59 Input unit setting screen" of 4 screen group and enter.
For current, voltage and mV input, set lower limit value, higher limit value and position of decimal point of display contents
for input signal.
(You should also select by 4-60, 4-61 and 4-62 screens by code.)
4. Control mode (PID) setting
For ON-OFF (2 position) action, select OFF by "2-1. Output 1 PID1 proportional band setting screen" of 2 screen group and enter.
Sets hysteresis by "2-2. Output 1 PID1 hysteresis setting screen."
If equipped with output 2, set by same method.
If using auto tuning (AT) with other than ON-OFF hysteresis, this setting operation is not required.
5. Control output characteristics setting
Select RA (for heating) or DA (for cooling) according to output specification (heating/cooling) on "4-45 Output 1 output
characteristics setting screen" and "4-48 Output 2 output characteristics setting screen" of 4 screen group and enter.
6. Event type setting
If equipped with event, select types of event on "4-2, 4-7 and 4-12 Event type setting screen" of 4 screen group and enter.
7. Analog output setting
If equipped with analog output, select items to be output as analog signals on "4-23 Analog output type setting screen" of 4
screen group and enter.
8. Precaution concerning initialization by data modification
Modifying measuring range code, type of event or type of analog output initializes related setting values (data). The data
must therefore be set again.
4.Measuring Range Codes:
Select measuring range from the following table.Changing the code initializes all data related to measuring range;
Input type |
Code |
Measuring range (°C) |
Measuring range (°F) |
Universal- Input |
Thermos couple
Kelvin
|
B |
01 *1 |
0 ~ 1800 °C |
0 ~ 3300 °F |
R |
02 |
0 ~ 1700 °C |
0 ~ 3100 °F |
S |
03 |
0 ~ 1700 °C |
0 ~ 3100 °F |
K |
04 *2 |
-199.9 ~ 400.0 °C |
-300 ~ 750 °F |
05 |
0.0 ~ 800.0 °C |
0 ~ 1500 °F |
06 |
0 ~ 1200 °C |
0 ~ 2200 °F |
E |
07 |
0 ~ 700 °C |
0 ~ 1300 °F |
J |
08 |
0 ~ 600 °C |
0 ~ 1100 °F |
T |
09 *2 |
-199.9 ~ 200.0 °C |
-300 ~ 400 °F |
N |
10 |
0 ~ 1300 °C |
0 ~ 2300 °F |
PLII *3 |
11 |
0 ~ 1300 °C |
0 ~ 2300 °F |
WRe5-26 *4 |
12 |
0 ~ 2300 °C |
0 ~ 4200 °F |
U *5 |
13 *2 |
-199.9 ~ 200.0 °C |
-300 ~ 400 °F |
L *5 K |
14 15 *6 |
0 ~ 600 °C 10.0 ~ 350.0 K |
0 ~ 1100 °F 10.0 ~ 350.0 K |
K |
15*6 |
|
|
AuFe-Cr |
16 *7 |
0.0 ~ 350.0 K |
0.0 ~ 350.0 K |
K |
17 *6 |
10 ~ 350 K |
10 ~ 350 K |
AuFe-Cr |
18 *7 |
0 ~ 350 K |
0 ~ 350 K |
R.T.D |
Pt100 |
30 |
-100.0 ~ 350.0 °C |
-150.0 ~ 650.0 °F |
31 |
-200 ~ 600 °C |
-300 ~ 1100 °F |
32 |
-100.0 ~ 100.0 °C |
-150.0 ~ 200.0 °F |
33 |
- 50.0 ~ 50.0 °C |
-50.0 ~ 120.0 °F |
34 |
0.0 ~ 200.0 °C |
0.0 ~ 400.0 °F |
JPt100 |
35 |
-200 ~ 500 °C |
-300 ~ 1000 °F |
36 |
-100.0 ~ 100.0 °C |
-150.0 ~ 200.0 °F |
37 |
- 50.0 ~ 50.0 °C |
-50.0 ~ 120.0 °F |
38 |
0.0 ~ 200.0 °C |
0.0 ~ 400.0 °F |
39 |
-100.0 ~ 350.0 °C |
-150.0 ~ 650.0 °F |
Pt100 |
40 |
-199.9 ~ 550.0 °C |
-300 ~ 1000 °F |
41 |
0.0 ~ 350.0 °C |
0.0 ~ 650.0 °F |
42 |
0.0 ~ 550.0 °C |
0 ~ 1000 °F |
JPt100 |
45 |
-199.9 ~ 500.0 °C |
-300 ~ 1000 °F |
46 |
0.0 ~ 350.0 °C |
0.0 ~ 650.0 °F |
47 |
0.0 ~ 500.0 °C |
0 ~ 1000 °F |
mV |
-10 ~ 10mV |
71 |
Initial value: 0.0 ~ 100.0 Input scaling setting range: -1999 ~ 9999 Span: 10 ~ 10,000 count Decimal point position: None, 1/2/3 digits following decimal point Lower limit value is less than higher limit value. NOTE: For current input, install input terminals of the specified receiving impedance (250 Ω) and use code 84 (0 ~ 20 mA) or 85 (4 ~ 20 mA). |
0 ~ 10mV |
72 |
0 ~ 20mV |
73 |
0 ~ 50mV |
74 |
10 ~ 50mV |
75 |
0 ~ 100mV |
76 |
Voltage |
V |
-1 ~ 1V |
81 |
0 ~ 1V |
82 |
0 ~ 2V |
83 |
0 ~ 5V |
84 |
1 ~ 5V |
85 |
0 ~10V |
86 |
Thermocouple: B, R, S, K, E, J, T, N: JIS/IEC R.T.D. Pt100: JIS/IEC JPt100
*1. Thermocouple B: Accuracy guarantee not applicable to 400°C (752°F) or below.
*2. Thermocouple K, T, U: Accuracy of those readings below -100°C is ±0.7% FS
*3. Thermocouple PLII: Platinel *4. Thermocouple WRe5-26: ASTM E988-96
*4. Thermocouple WRe5-26: ASTM E988-96
*5. Thermocouple U, L: DIN 43710
*6. Thermocouple K (Kelvin) accuracy (Temperature range)
10.0 ~ 30.0 K ± (2.0%FS + [CJ error × 20] K + 1K)
30.0 ~ 70.0 K ± (1.0%FS + [CJ error × 7] K + 1K)
70.0 ~ 170.0 K ± (0.7%FS + [CJ error × 3] K + 1K)
170.0 ~ 270.0 K ± (0.5%FS + [CJ error × 1.5] K + 1K)
270.0 ~ 350.0 K ± (0.3%FS + [CJ error × 1] K + 1K)
*7. Thermocouple Metal-chromel (AuFe-Cr) (Kelvin) accuracy(Temperature range)
0.0 ~ 30.0 K ± (0.7%FS + [CJ error × 3] K + 1K)
30.0 ~ 70.0 K ± (0.5%FS + [CJ error × 1.5] K + 1K)
70.0 ~ 170.0 K ± (0.3%FS + [CJ error × 1.2] K + 1K)
170.0 ~ 280.0 K ± (0.3%FS + [CJ error × 1] K + 1K)
280.0 ~ 350.0 K ± (0.5%FS + [CJ error × 1] K + 1K)
NOTE: Unless otherwise specified, the measuring range will be set as follows when shipped from the factory:
Input |
Standard/rating |
Measuring range |
Multi input |
K thermocouple |
0.0 ~ 800.0°C |
Voltage (V) |
0 ~ 10V DC |
0.0 ~ 100.0, no unit |
5.Packing & Delivery:
6. FAQ
Q1.What advantages do you have?
A1. Solex is the direct Manufacturer in Cangzhou city, China, we have professional developing, marketing & production team to offer you the most competitive price and best service.
Q2. What's your main product?
A2. We have three product series~solid state relay, thyristor regulator(power &voltage), Wafer making furnace heater;
Q3. Could you print our own logo?
A3. Yes, our company are available for Retail & Wholesale & OEM & ODM.
Q4. How long is the quality guarantee?
A4. 18 month warranty, our products are 100% inspected before leaving factory.
Q5. How long is the deliver time?
A5. It usually takes about 3 - 5 working days for sample order and 10 - 25 days for big order.
Q6. What is your payment terms?
A6. T/T, Western Union, Money Gram, L/C at sight,etc.
Q7. Any certification of your company or product?
A7.We have ISO 9001,CE,CB,TUV, etc.