Customization: | Available |
---|---|
Customized: | Customized |
Certification: | RoHS, CB, CCC, ISO9001, CE |
Still deciding? Get samples of US$ 270/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Name of terminal |
Description | Terminal No. | |
SRS1 | SRS3/4/5 | ||
Power supply | 100-240 V AC 100-240 V AC |
7 8 |
13 14 |
Input | RTD: A, thermocouple/voltage: + RTD: B, thermocouple/voltage: - RTD: b |
4 5 6 |
22 23 24 |
Control output 1 |
Contact: NO, SSR drive voltage/voltage/current: + Contact: NO, SSR drive voltage/voltage/current: - |
9 10 |
15 16 |
Event output | COM EV1 EV2 |
1 2 3 |
19 20 21 |
External control input/DI |
COM DI1 |
11 12 |
17 18 |
Name | Function |
1) Measured value (PV) display | 1. Measured value display LED (red) Displays current measured value (PV) on basic screen (screen 0-0). Displays type of parameter on each respective parameter display screen. |
2) Target set value (SV) display | 2. Target value display LED (green) Displays current target set value (SV) on basic screen (screen 0-0). Displays setting values on each respective parameter setting screen. |
3) Action display | Displays status of controller. RUN: Action display LED (green) Off: Control halt status (standby or reset) On: Running by fixed value control status (FIX) Flashing: Running by program control status (RUN) OUT: Control output (green) For output by contact or SSR drive voltage: Off: Output is OFF. On: Output is ON. For voltage/current output: Off when output is 0% and On when output is 100%. In other cases, flashes at intervals of 0.5 seconds (multiples of 0.5 sec.). AT: Auto tuning LED (green) Off: Auto tuning not executed On: Auto tuning standby Flashing: Auto tuning being executed MAN: Manual control LED (green) Off: Automatic control operating status Flashing: Manual control operating status EV1: Event output 1 (orange) EV2: Event output 2 (orange) Off: Event output is OFF. On: Event output is ON. |
4) Operating keys | Parameter key Displays the next screen in various screen groups. Down key Decrements setting values. Up key Increments setting values. Enter key Enters setting values. Displays various screen groups if no SV values are being modified on the basic screen. |
Input type | Code | Measuring range (°C) Measuring range ( ) | |||
Kelvin | B *6 | *1 | 0-1800°C 0-3300 | ||
R | -50-1700°C 0-3100 | ||||
S | 0-1700°C 0-3100 | ||||
K | *2 | -199.9-400.0°C -300-750 | |||
0-1370°C 0-2500 | |||||
E | 0-700°C 0-1300 | ||||
J | *2 | -200-600°C -320-1100 | |||
T *6 | *2 | -270-400°C -450-750 | |||
N | 0-1300°C 0-2300 | ||||
PL ll *3 | 0-1300°C 0-2300 | ||||
C(WRe5-26) | 0-2300°C 0-4200 | ||||
U *3 | *2 | -199.9-400.0°C -300-750 | |||
L K |
*4 | 0-600°C 0-1100 10.0-350.0K |
|||
AuFe-Cr | *5 | 0.0-350.0K | |||
RTD | Pt100 | -199.9-300.0°C | -300-600 | ||
mV | -10-50 mV | Scaling range: -1999-9999 digit Span: 9999 digit |
|||
Voltage | V | 0-10 V |
Input range | Code | Measuring range |
Multi-input | K 0-1370°C | |
Voltage input | 0-10 V |